Overview

Data Logger with Ethernet Interface

Operate A Live Datalogger

Features:

  • Use Common Web Browser
  • View Real Time Instrument Reading
  • View Historical Trend Data
  • No Special Software Required
  • Configure Using Web Browser
  • 22 Days of 1 Minute Data
  • Download History Data to Excel
  • SCADA Ready (ModbusTCP)
  • User Selectable Logging Period
  • Real Time Date/Time Clock
  • User Configurable LAN Settings
  • Password Protected Configuration

Specifications
Model Number:EDL-01
Dimensions:2.5"x2.5"x1.0"
LAN Interface:10/100 Mbps
LAN Connector:RJ45
Protocols:HTTP, ModbusTCP
Sensor Interface:4-20mA
A/D Accuracy:12 bit, +/- 0.50% FS
Sensor Connector:8-Pin Terminal Block
Power:9 to 24 vdc, 300mA
Data Storage:31,680 Data Values
Logging Period:1 to 1440 Minutes
Data Table Format:HTML, CSV, Excel
Default IP Address:192.168.1.250
Operation Temp.:32 to 131 Deg F
Storage Temp.:-4 to 185 Deg F
Relative Humidity:5 to 95%
EMC Approvals:CE & FCC Class A
Warranty:1 Year, Limited

Terminations
PINSignals
3Sensor Ground
3Power Ground
4Power 9 to 24 vdc
5Sensor Power
PINSignals
1Tx+
2Tx-
3Rx+
6Rx-
Typical Application Wiring